Yodify Product Library
Add the Safety Analog Input Module HART Ex i Inputs, 8/6-Channels Series 9462 to your store or catalog
Book Your Demo and See How
or create your store
Safety Analog Input Module HART Ex i Inputs, 8/6-Channels Series 9462
Brand: R. STAHL AGThe 9462 series HART safety Analog Input Module for Zone 1 has six or eight channels for Ex i operating and supplying failsafe two-conductor HART transmitters with 0/4 to 20 mA signals in functionally safe circuits up to SIL 2.
It functions as a PROFIsafe slave in the remote I/O system and supports bidirectional HART communication.
All inputs are individually monitored to check for wire breakage/short-circuiting.
Features- For applications up to SIL 2 using PROFIsafe in Zone 1
- six or eight channels for two-conductor HART transmitters
- intrinsically safe Ex i IIC inputs with line fault monitoring
1 - 2 of 2 Part Numbers

162429
For applications up to SIL 2 using PROFIsafe in Zone 1
six or eight channels for two-conductor HART transmitters
intrinsically safe Ex i IIC inputs with line fault monitoring
Ambient Conditions
- Ambient temperature - -20 °C ... +65 °C
- Ambient temperature max. - +65 °C
- Ambient temperature min. - -20 °C
Auxiliary power
- Power consumption max. - 6.60 W
Electrical Data
- Input nominal signal range - 4 - 20 mA
Explosion Protection
- Application range (Zone) Note - A suitable enclosure in accordance with the area of application must be used. Refer to the operating instructions.
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 99 ATEX 2175
- ATEX gas certificate - PTB 99 ATEX 2175
- Certificate EAC - TS RU S-DE.AA71.B.00033
- Certificates - ATEX (PTB), Canada (FM), EAC (STV), IECEx (PTB), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 2 (1) G Ex ib [ia Ga] IIC T4 Gb
- Gas explosion protection EAC - 1 Ex ib [ia Ga] IIC T4 Gb X
- Gas explosion protection IECEx - Ex ib [ia Ga] IIC T4 Gb
- IECEX dust certificate - PTB 06.0001 X
- IECEX gas certificate - PTB 06.0001 X
- Installation in Division NEC 500 - (Class I, II, III) 1, 2
- Ship approval - ABS, CCS, ClassNK, DNVGL, RINA
General
- Functional Description - The 9462 series HART safety Analog Input Module for Zone 1 has six or eight channels for Ex i operating and supplying failsafe two-conductor HART transmitters with 0/4 to 20 mA signals in functionally safe circuits up to SIL 2. It functions as a PROFIsafe slave in the remote I/O system and supports bidirectional HART communication. All inputs are individually monitored to check for wire breakage/short-circuiting.
- Highlights - For applications up to SIL 2 using PROFIsafe in Zone 1 six or eight channels for two-conductor HART transmitters intrinsically safe Ex i IIC inputs with line fault monitoring
- Product Description - Remote I/O IS1+ Safety Analog Input Module HART
- Product Type - 9462/12-08-11
- Title Product Variant Technical Data - 9462/12-08-11 Safety Analog Input Mod. H
- Version 2 - For SIL type 2-conductor HART
- Version 3 - Transmitter
- WebCode - 9462A
Input
- Supply voltage input - 16 V
Mechanical Data
- Version - Ex i input, 8 channels
- Weight - 0.380 kg
Safety Data
- Max. Current I o - 91.0 mA
- Max. Power P o - 589.000 mW
- Max. Voltage U o - 26.20 V

167543
For applications up to SIL 2 using PROFIsafe in Zone 1
six or eight channels for two-conductor HART transmitters
intrinsically safe Ex i IIC inputs with line fault monitoring
Ambient Conditions
- Ambient temperature - -20 °C ... +65 °C
- Ambient temperature max. - +65 °C
- Ambient temperature min. - -20 °C
Auxiliary power
- Power consumption max. - 6.60 W
Electrical Data
- Input nominal signal range - 4 - 20 mA
Explosion Protection
- Application range (Zone) Note - A suitable enclosure in accordance with the area of application must be used. Refer to the operating instructions.
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 99 ATEX 2175
- ATEX gas certificate - PTB 99 ATEX 2175
- Certificate EAC - TS RU S-DE.AA71.B.00033
- Certificates - ATEX (PTB), EAC (STV), IECEx (PTB), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 2 (1) G Ex ib [ia Ga] IIC T4 Gb
- Gas explosion protection EAC - 1 Ex ib [ia Ga] IIC T4 Gb X
- Gas explosion protection IECEx - Ex ib [ia Ga] IIC T4 Gb
- IECEX dust certificate - PTB 06.0001 X
- IECEX gas certificate - PTB 06.0001 X
- Installation in Division NEC 500 - (Class I, II, III) 1, 2
- Ship approval - ABS, CCS, ClassNK, DNVGL, RINA
General
- Functional Description - The 9462 series HART safety Analog Input Module for Zone 1 has six or eight channels for Ex i operating and supplying failsafe two-conductor HART transmitters with 0/4 to 20 mA signals in functionally safe circuits up to SIL 2. It functions as a PROFIsafe slave in the remote I/O system and supports bidirectional HART communication. All inputs are individually monitored to check for wire breakage/short-circuiting.
- Highlights - For applications up to SIL 2 using PROFIsafe in Zone 1 six or eight channels for two-conductor HART transmitters intrinsically safe Ex i IIC inputs with line fault monitoring
- Product Description - Remote I/O IS1+ Safety Analog Input Module HART
- Product Type - 9462/12-06-11
- Title Product Variant Technical Data - 9462/12-06-11 S-AIM HART
- Version 2 - For SIL type 2-conductor HART
- Version 3 - Transmitter
- WebCode - 9462A
Input
- Supply voltage input - 16 V
Mechanical Data
- Version - Ex i input, 6 channels
- Weight - 0.380 kg
Safety Data
- Max. Current I o - 91.0 mA
- Max. Power P o - 589.000 mW
- Max. Voltage U o - 26.20 V
1 - 2 of 2 Part Numbers